FAA L830 Transformer Qualification

4.2.2 Shock Test (confirmation)

Transformer secondary currents were rechecked, and they met the requirements as can be seen in the following table:

Secondary Current
Sample Before
Amperes AC
After
Amperes AC
Difference Specification
1 6.563 6.565 0.03 % < 1 %
2 6.565 6.566 0.03 % < 1 %
3 6.561 6.563 0.03 % < 1 %